Do heat pumps work in an Oxford or Norfolk winter?
Yes, when it's a cold climate model sized for your house. Here are the local numbers an installer should size to, and what to expect on the coldest nights.
How cold it gets here
Ontario's Building Code sets a winter design temperature for each place: the temperature a heating system must handle. Only the coldest 2.5% of January hours are colder.1
| Place | January design (2.5%) | January 1% | Heating degree-days |
|---|---|---|---|
| Woodstock | -19°C | -21°C | 3,910 |
| Ingersoll | -18°C | -20°C | 3,920 |
| Tillsonburg | -17°C | -19°C | 3,840 |
| Simcoe | -17°C | -19°C | 3,700 |
| Nanticoke (Port Dover) | -15°C | -17°C | 3,600 |
The Building Code doesn't list Norwich or Delhi. Use the nearest towns above. Heating degree-days measure how much heating a winter needs; higher means more.
What the rebate demands of the equipment
To earn the Ontario rebate, a cold climate heat pump must still deliver at least 70% of its rated heating output at -15°C, at an efficiency of 1.8 or better. That means 1.8 units of heat for each unit of electricity, at a temperature where baseboard heaters manage 1. It must also be variable speed and on Natural Resources Canada's eligible list.2
What a real test showed
Natural Resources Canada tested a cold climate heat pump in a research house in Ottawa, designed for -25°C, colder than any town on this site. Its efficiency ranged from an average of 1.5 at -21.1°C to 3.0 at +4.9°C. With a 10 kW electric backup heater, it kept the house comfortable at the coldest temperatures of the test, below -21°C, though indoor temperatures swung more than with a standard system, and the supply air cooled during defrost until the backup warmed it.3 The test was published in 2013 and covered one unit.
Backup heat, by fuel
- Oil: the heat pump takes over and electric backup is allowed. The oil tank is emptied or removed by a TSSA-registered contractor.2
- Propane: you can keep the propane furnace as backup in a hybrid system and still get the full rate. You sign a tank attestation.
- Natural gas: a gas furnace or boiler can stay as backup, at the gas rate of $500 per ton.
- Wood or electric baseboard: you can keep them as backup.
Sizing is the whole game
The Ontario rebate requires the contractor to size the system with Natural Resources Canada's sizing tool, for the whole home including the basement.2 Ask to see that sizing form with your quote. An undersized system leans on backup heat; an oversized one costs more up front.
Common questions
Will a heat pump keep my house warm at -20°C?
Do I need backup heat?
What happens during defrost?
Sources
- Ontario 2024 Building Code Compendium: SB-1 Climatic and Seismic Data, accessed 2026-11-21
- Home Renovation Savings Program: Heat Pump Program Stream Requirements (May 2025), linked from the program's terms and conditions, accessed 2026-11-21
- Natural Resources Canada: Cooling and Heating Season Performance Assessment of a cold climate air source heat pump at the Canadian Centre for Housing Technology (2013), accessed 2026-11-21
Figures checked November 21, 2026. Programs change; confirm the current rules on the program page before you buy.